LW26GS series Pad-lock type switches are derivatives of LW26 series rotary switches. Installed in equipment where it requires a pad-lock to lock the switch in certain position. For instance, to fix the switch in ON position, to avoid the unauthorized personnel from operating the switch. LW26GS series Pad-lock type switch complies with the GB 14048.3 and IEC 60947.3.
Classification 1) LW26GS series Pad-lock type switches have four current ratings: 20A, 25A, 32A and 63A. LW26GS-20 has two escutcheon plate types, small escutcheon plate and large escutcheon plate. Others have only large escutcheon plate. Please check out the Dimensions and installation for details. The figure 1 represents small escutcheon plate, and 2 represents large escutcheon plate. Small escutcheon plate allows two pad-locks and large escutcheon plate allows three pad-locks. 2) LW26GS series Pad-lock switches have Quick-stop and Normal if classified by operation. Normal(LW26GS↓/03) has Black escutcheon plate and Black handle. Quick-stop(LW26GS↓/04) has Red escutcheon plate and Red handle.
Technical parameters
Description |
|
LW26GS-20 |
LW26GS-25 |
LW26GS-32 |
LW26GS-63 |
Rated working voltage Ue |
V |
440 |
440 |
440 |
440 |
Rated thermal current Ith |
A |
20 |
25 |
32 |
63 |
Rated working current Ie |
|
AC-21A |
A |
20 |
25 |
32 |
63 |
AC-22A |
A |
20 |
25 |
32 |
63 |
AC-23A |
A |
15 |
22 |
30 |
57 |
Power P |
|
AC-23A |
KW |
7.5 |
11 |
15 |
30 |
Operation |
|
Non-load |
|
8500 |
8500 |
8500 |
8500 |
Load |
|
1500 |
1500 |
1500 |
1500 |
Total |
|
10000 |
10000 |
10000 |
10000 |
Dimension and installation LW26GS-20/↓-1 Small escutcheon plate
LW26GS-↓/↓-1 Large escutcheon plate
LW26GS-↓/↓-2
Deiscription |
Dimension (mm) |
A1 |
L1 |
D1 |
A2 |
L2 |
D2 |
LW26GS-20 |
43 |
43 |
朴8.5 |
43 |
37.5 |
朴45 |
LW26GS-25 |
45.2 |
51 |
朴8.5 |
45.2 |
45 |
朴47 |
LW26GS-32 |
58 |
55 |
朴10 |
|
|
|
LW26GS-63 |
66 |
72.5 |
朴10 |
|
| |